Watts to Amps Calculator
For DC or single-phase AC at PF = 1: Amps = Watts ÷ Volts.
4800 watts is 40 amps at 120V, about 23.08 amps at 208V, or 20 amps at 240V for single-phase AC at power factor (PF) = 1. Choose the circuit type and actual power factor below for other loads.
Updated · Calculated examples; sources and assumptions below.
How many amps is 4800 watts?
| Watts | Voltage across load | Current |
|---|---|---|
| 4,800W | 120V | 40A |
| 4,800W | 208V | 23.08A |
| 4,800W | 240V | 20A |
For example, 4,800 ÷ 240 = 20A. At the same input watts and PF, a higher voltage means less current. Use the voltage across the actual load, not a different voltage available elsewhere in the supply system.
At the same 4,800W and 240V, lowering PF from 1 to 0.8 raises current from 20A to 25A: 4,800 ÷ (240 × 0.8) = 25. That is 25% more current for the same real input power, not a statement that 20% of the input watts is lost as heat.
Common conversions
| Input watts | Amps at 120V | Amps at 208V | Amps at 240V |
|---|---|---|---|
| 600W | 5A | 2.88A | 2.5A |
| 1,200W | 10A | 5.77A | 5A |
| 1,725W | 14.38A | 8.29A | 7.19A |
| 1,800W | 15A | 8.65A | 7.5A |
| 2,400W | 20A | 11.54A | 10A |
| 3,600W | 30A | 17.31A | 15A |
| 7,200W | 60A | 34.62A | 30A |
| 11,000W | 91.67A | 52.88A | 45.83A |
| 19,000W | 158.33A | 91.35A | 79.17A |
11,000 watts at 240V is about 45.83 amps for single-phase AC at PF = 1. The 1,725W and 19,000W rows show why queries without a voltage need more than one answer; lower PF also increases current at the same real input watts and voltage.
Choose the formula for your circuit
| Circuit | Formula | Inputs |
|---|---|---|
| DC | I = P ÷ V | DC voltage and current; power factor does not apply. |
| Single-phase AC | I = P ÷ (V × PF) | RMS voltage across the load, RMS current and power factor. |
| Balanced three-phase AC | I = P ÷ (√3 × V × PF) | Total three-phase input watts, line-to-line RMS voltage and line current. |
A 208V supply does not by itself tell you which mode to use. A single-phase load connected across two lines uses the single-phase formula; a balanced three-phase load uses the three-phase formula. For an unbalanced load, calculate or measure the individual phases instead.
What is power factor?
Power factor (PF) = real input power (W) ÷ apparent power (VA). It is not the motor's efficiency, which compares mechanical output with electrical input. For a consuming AC load, PF is between 0 and 1; converting positive watts to amps requires PF greater than zero.
A resistive heater can be modeled at PF = 1. Motors, compressors and electronic power supplies can have different power factors depending on the equipment and operating load. Use documented or measured input values; the calculator's default of 1 is an assumption, not a verified value for your appliance.
Use electrical input watts, not a motor's mechanical output rating. These formulas estimate operating power or current; they do not predict compressor startup surge.
A conversion is not a breaker recommendation
Calculated amps alone do not establish a safe breaker, wire size or equipment pairing. Load duration, other loads on the circuit, startup current, equipment instructions and applicable electrical requirements also matter. Check the appliance nameplate and manufacturer documentation; have circuit selection verified by a qualified electrician.
Sources and assumptions
Reference: Fluke's power factor definition and balanced three-phase power explanation. The examples on this page are calculated reference cases, not appliance measurements or installation approvals.
FAQ
How do I convert watts to amps?
For DC, divide input watts by volts. For single-phase AC, divide by volts × PF. For balanced three-phase AC, divide total input watts by √3 × line-to-line volts × PF.
Is 4800W at 208V always 23.08A?
No. That answer assumes a single-phase load at PF = 1. A balanced three-phase load drawing 4,800W total at 208V line-to-line and PF = 1 draws about 13.32A per line. Select the mode that matches the load.
How many amps is 1500 watts at 120V?
12.5 amps. That is the arithmetic for a resistive load; check the appliance instructions and circuit limits before connecting it.