Wire Size Calculator
Smallest copper gauge with under 3% voltage drop
A 30A load 25ft from a 12V battery needs at least 8 AWG copper. Low-voltage DC systems lose a much larger share of their voltage to wire resistance than mains circuits — the 3% drop rule (NEC guidance for sensitive loads) is the standard screen: keep the round-trip drop under 3% of system voltage, or the load sees brown-out behavior and the wire wastes your stored energy as heat.
Updated · Calculated examples; assumptions and safety notes below.
Worked examples at the 3% drop rule
| 10A | 15 ft | 12V | AWG 10 |
| 30A | 25 ft | 12V | AWG 2 |
| 30A | 25 ft | 24V | AWG 6 |
| 10A | 40 ft | 48V | AWG 12 |
| 100A | 10 ft | 48V | AWG 8 |
This calculator sizes for voltage drop only. Wire must also satisfy ampacity (current-heat) ratings for its insulation and bundling — for the gauges listed here at these currents the 3% rule is usually the binding constraint, but always check the ampacity table for your insulation temperature rating.
FAQ
Why does 12V need such thick wire?
At 12V the 3% drop allowance is only 0.36V. The same amps over the same distance at 48V get 1.44V of allowance — 4× looser. This is why serious solar builders move banks to 24V or 48V: the wire requirement drops by half or more.
Is this the same as AC wire sizing?
No — this calculator models DC resistance on the round trip. AC branch circuits follow NEC ampacity tables and different derating rules. Do not use this tool for household mains wiring; consult a licensed electrician.
What does the round trip mean?
Current flows out on the positive conductor and back on the negative, so a "25ft run" means 50ft of wire carrying current. The calculator doubles your one-way length automatically.