Inverter Size Calculator

Cover continuous load with 25% headroom, and the surge — whichever is higher

A 900W continuous load with a 2,700W startup surge needs an inverter rated ~2,700W or higher. Two different limits must both pass: the continuous rating covers sustained running draw (with headroom for efficiency loss and long sessions), and the surge rating covers the largest motor start — a compressor or pump pulls 2–6× its running power for a second or two at startup.

Updated · Calculated examples; assumptions and safety notes below.

Your numbers, clearly calculated
Continuous rating with 25% headroom1,125 W
Surge that must also be covered2,700 W
Recommended inverter rating2,700 W

Worked examples

<tr><th scope="col">Scenario</th><th scope="col">Continuous</th><th scope="col">Surge</th><th scope="col">Inverter rating</th></tr>
Computed by the calculator's rules: max(continuous × 1.25, surge). Verify your devices' actual surge before buying.
Fridge + router + lights300W1,200W (compressor)1,200W
Well pump (½HP class)1,000W3,000W3,000W
Office: PC + monitors450W700W~565W
Continuous load only (no motor)2,500Wn/a3,125W

Surge figures here are planning examples. Real startup demand must come from each appliance's locked-rotor or inrush data — our appliance library records verified surge figures per device, and pure-sine output is required by most electronics and motors.

FAQ

What size inverter do I need for a fridge?

Sum the fridge's running watts and its startup surge. An Energy Star fridge runs ~125W but starts at ~1,200W: the surge is the binding number, so a 1,200W+ pure-sine inverter covers it. Our refrigerator guide has the verified figures.

Why 25% headroom on the continuous load?

Inverters lose efficiency as loads approach their rating (heat, fan throttle), and real loads drift above nameplate. Sizing at exactly 100% of measured load runs the inverter at its thermal edge indefinitely — the 25% margin keeps it in the efficient, quiet band.

Does a bigger inverter waste power?

Slightly — larger units have higher idle draw. Size for your real load plus headroom, not "as big as possible". A 3,000W inverter idling for a 100W load wastes meaningful stored energy overnight.