VA to Watts Calculator

Watts = VA × Power Factor

1,500 VA is 1,200W at power factor (PF) 0.8, or 1,500W at PF 1.0. PF 0.8 is an example assumption; use the equipment's documented or measured PF for your calculation. VA measures apparent power; for single-phase AC it equals RMS voltage × RMS current. Watts measure real electrical input power, and PF = W ÷ VA.

Updated · Arithmetic by definition; choosing the right PF is the real task, see guidance below.

Your numbers, clearly calculated
Real power1,200 W

VA to watts conversion table

Real power (W) for common VA ratings at three example power factors. PF 1.0 applies to modeled resistive loads (heaters, incandescent); PF 0.8 is an example assumption, not a safe default for unknown equipment.
VAPF 1.0PF 0.8PF 0.6
75 VA75W60W45W
500 VA500W400W300W
650 VA650W520W390W
800 VA800W640W480W
900 VA900W720W540W
1,000 VA1,000W800W600W
1,500 VA1,500W1,200W900W
2,000 VA2,000W1,600W1,200W
3,000 VA3,000W2,400W1,800W
5,000 VA5,000W4,000W3,000W
7,500 VA7,500W6,000W4,500W
10,000 VA10,000W8,000W6,000W

Why the two ratings exist

Inverters and generators carry both limits: a W rating for real power (engine/alternator capacity) and a VA or current rating for apparent power (wiring and semiconductor thermal limits). A 1,200W load at PF 0.8 draws 1,500VA — inside the W limit of a "1,200W" unit, but at its apparent-power edge. This is the same discipline our sizing engine applies: recorded VA startup demands (nameplate LRA × voltage) are screened against both limits and never silently equated with watts.

FAQ

What's the difference between VA and watts?

VA (volt-amps) is apparent power. Watts measure real electrical input power. Power factor is their ratio: PF = W ÷ VA. A motor drawing 1,500VA at PF = 0.8 consumes 1,200W of real input power; its mechanical output also depends on motor efficiency.

Why does this matter for generators?

Check both real-power output and apparent-power or current limits, along with voltage and startup capability. A 1,200W load at PF = 0.8 draws 1,500VA; a W-only label does not establish that a generator or inverter can supply it.

What power factor should I use?

Use a documented or measured PF for the equipment and operating load. A resistive heater can be modeled at PF = 1. Motor and electronic loads vary; the calculator's 0.8 default is an example, not a safe bound for unknown equipment. PF does not represent motor efficiency or predict startup surge.

How do I convert watts back to VA?

Divide by the same power factor: VA = W ÷ PF. 800W at PF 0.8 is 1,000VA. If you don't know the PF, you cannot convert — a range of plausible PFs (0.6–1.0) spans a 40% spread in the answer, which is why equipment documentation beats any default.

Is higher power factor better?

For the grid and the wiring, yes: higher PF means less current for the same real power. It is not a measure of equipment quality or efficiency — a PF 0.6 device is not "losing" 40% of its energy; the extra current returns to the source each cycle. What it does cost is current capacity in your inverter, extension cords and breakers.